EEPROM-analyse
Bekijk de EEPROM-parameters van een warmtepomp of vergelijk twee apparaten
Apparaten met dump
16
Registers met naam
291 / 512
Onbekende registers
221
Verschillen
–
2d4049
Amber 120
- Firmware
- 0.9.0
- Programma
- 286
- EEPROM
- 114 (201/146)
- Uitgelezen
- 18 sep 2026 17:16
Registers
512 registers van dit apparaat
| Register | Naam | Waarde |
|---|---|---|
| 3000 | EEPROM data length / CRC start byte (0x000) | 255 |
| 3001 | Cooling frequency F0 | 0 |
| 3002 | Cooling frequency F1 | 20 |
| 3003 | Cooling frequency F2 | 26 |
| 3004 | Cooling frequency F3 | 30 |
| 3005 | Cooling frequency F4 | 36 |
| 3006 | Cooling frequency F5 | 43 |
| 3007 | Cooling frequency F6 | 48 |
| 3008 | Cooling frequency F7 | 55 |
| 3009 | Cooling frequency F8 | 69 |
| 3010 | Cooling frequency F9 | 74 |
| 3011 | Cooling frequency F10 | 82 |
| 3012 | Heating frequency F0 | 0 |
| 3013 | Heating frequency F1 | 28 |
| 3014 | Heating frequency F2 | 36 |
| 3015 | Heating frequency F3 | 43 |
| 3016 | Heating frequency F4 | 55 |
| 3017 | Heating frequency F5 | 61 |
| 3018 | Heating frequency F6 | 67 |
| 3019 | Heating frequency F7 | 72 |
| 3020 | Heating frequency F8 | 79 |
| 3021 | Heating frequency F9 | 85 |
| 3022 | Heating frequency F10 | 90 |
| 3023 | Compressor start plateau 1 frequency (Hz) | 55 |
| 3024 | Compressor start plateau 2 frequency (Hz) | 55 |
| 3025 | 4-way valve polarity (0=reverse/cool, 1=normal/heat) | 0 |
| 3026 | Onbekend | 0 |
| 3027 | Onbekend | 0 |
| 3028 | UART1 inverter protocol extended frame option | 0 |
| 3029 | EEV control mode (0=ext, 3=SH+cascade, 5=ambient band) | 5 |
| 3030 | Target superheat heating ambient < -15C (mode 5) | 20 |
| 3031 | Target superheat heating ambient -15 to -5C (mode 5) | 20 |
| 3032 | Target superheat heating ambient -5 to 5C (mode 5) | 25 |
| 3033 | Target superheat heating ambient 5 to 10C (mode 5) | 30 |
| 3034 | Target superheat heating ambient 10 to 30C (mode 5) | 35 |
| 3035 | Target superheat heating ambient >= 30C (mode 5) | 30 |
| 3036 | Target superheat offset water < 35C (mode 5) | 5 |
| 3037 | Target superheat offset water >= 55C (mode 5) | 5 |
| 3038 | EEV start correction at low water temp | 11 |
| 3039 | Onbekend | 0 |
| 3040 | Crankcase heater max on-time ambient >= -15C | 3 |
| 3041 | Crankcase heater max on-time ambient -20 to -15C | 6 |
| 3042 | Crankcase heater max on-time ambient -30 to -20C | 12 |
| 3043 | Crankcase heater max on-time ambient < -30C | 18 |
| 3044 | Crankcase heater min off-time before restart | 2 |
| 3045 | EEV start heating: water < 30C, ambient -15 to -10C | 170 |
| 3046 | EEV start heating: water < 30C, ambient < -20C | 170 |
| 3047 | EEV start heating: water 30-45C, ambient -15 to -10C | 190 |
| 3048 | EEV start heating: water 30-45C, ambient < -20C | 190 |
| 3049 | EEV start heating: water >= 45C, ambient -15 to -10C | 195 |
| 3050 | EEV start heating: water >= 45C, ambient < -20C | 195 |
| 3051 | Onbekend | 0 |
| 3052 | Onbekend | 0 |
| 3053 | Onbekend | 0 |
| 3054 | Onbekend | 0 |
| 3055 | Onbekend | 0 |
| 3056 | Onbekend | 0 |
| 3057 | Onbekend | 0 |
| 3058 | Onbekend | 0 |
| 3059 | Onbekend | 0 |
| 3060 | Onbekend | 0 |
| 3061 | Onbekend | 0 |
| 3062 | Onbekend | 0 |
| 3063 | Onbekend | 0 |
| 3064 | Onbekend | 0 |
| 3065 | Onbekend | 0 |
| 3066 | Onbekend | 0 |
| 3067 | Onbekend | 0 |
| 3068 | Onbekend | 0 |
| 3069 | Onbekend | 0 |
| 3070 | Onbekend | 0 |
| 3071 | Onbekend | 0 |
| 3072 | Onbekend | 0 |
| 3073 | Onbekend | 0 |
| 3074 | Onbekend | 0 |
| 3075 | Onbekend | 0 |
| 3076 | Onbekend | 0 |
| 3077 | Onbekend | 0 |
| 3078 | Onbekend | 0 |
| 3079 | Onbekend | 0 |
| 3080 | Oil return interval heating ambient 0-14C (min) | 170 |
| 3081 | Onbekend | 0 |
| 3082 | Onbekend | 0 |
| 3083 | Onbekend | 0 |
| 3084 | Onbekend | 0 |
| 3085 | Extra input / R290 leak detector timer (min, V2) | 0 |
| 3086 | Onbekend | 0 |
| 3087 | Onbekend | 0 |
| 3088 | Max compressor step heating subband 1 (V2) | 0 |
| 3089 | Max compressor step heating subband 2 (V2) | 0 |
| 3090 | Max compressor step heating subband 3 (V2) | 0 |
| 3091 | Onbekend | 0 |
| 3092 | Onbekend | 0 |
| 3093 | Onbekend | 0 |
| 3094 | Onbekend | 0 |
| 3095 | Onbekend | 0 |
| 3096 | Onbekend | 0 |
| 3097 | Onbekend | 0 |
| 3098 | Soft low pressure threshold (0.1 bar, V2) | 0 |
| 3099 | Soft low pressure timer (min, V2) | 0 |
| 3100 | Soft low pressure max compressor step (V2) | 0 |
| 3101 | Onbekend | 0 |
| 3102 | Onbekend | 0 |
| 3103 | Condensation temp limit heating 1 (V2) | 0 |
| 3104 | Condensation temp limit heating 2 (V2) | 0 |
| 3105 | Onbekend | 0 |
| 3106 | Onbekend | 0 |
| 3107 | Onbekend | 0 |
| 3108 | Onbekend | 0 |
| 3109 | Onbekend | 0 |
| 3110 | Onbekend | 0 |
| 3111 | Onbekend | 0 |
| 3112 | Onbekend | 0 |
| 3113 | Onbekend | 0 |
| 3114 | Onbekend | 0 |
| 3115 | Onbekend | 0 |
| 3116 | Onbekend | 0 |
| 3117 | Onbekend | 0 |
| 3118 | Onbekend | 0 |
| 3119 | Onbekend | 0 |
| 3120 | Onbekend | 0 |
| 3121 | Onbekend | 0 |
| 3122 | Onbekend | 0 |
| 3123 | Onbekend | 0 |
| 3124 | Onbekend | 0 |
| 3125 | Onbekend | 0 |
| 3126 | Onbekend | 0 |
| 3127 | Onbekend | 0 |
| 3128 | Onbekend | 0 |
| 3129 | Onbekend | 0 |
| 3130 | Onbekend | 0 |
| 3131 | Onbekend | 0 |
| 3132 | Onbekend | 0 |
| 3133 | Onbekend | 0 |
| 3134 | Onbekend | 0 |
| 3135 | Onbekend | 0 |
| 3136 | Onbekend | 0 |
| 3137 | Onbekend | 0 |
| 3138 | Onbekend | 0 |
| 3139 | Onbekend | 0 |
| 3140 | Onbekend | 0 |
| 3141 | Onbekend | 0 |
| 3142 | Onbekend | 0 |
| 3143 | Onbekend | 0 |
| 3144 | Onbekend | 0 |
| 3145 | Onbekend | 0 |
| 3146 | Onbekend | 0 |
| 3147 | Onbekend | 0 |
| 3148 | Onbekend | 0 |
| 3149 | Onbekend | 0 |
| 3150 | Onbekend | 0 |
| 3151 | Onbekend | 0 |
| 3152 | Onbekend | 0 |
| 3153 | Onbekend | 0 |
| 3154 | Onbekend | 0 |
| 3155 | Onbekend | 0 |
| 3156 | Onbekend | 0 |
| 3157 | Onbekend | 0 |
| 3158 | Onbekend | 0 |
| 3159 | Onbekend | 0 |
| 3160 | Onbekend | 0 |
| 3161 | Onbekend | 0 |
| 3162 | Onbekend | 0 |
| 3163 | Onbekend | 0 |
| 3164 | Onbekend | 0 |
| 3165 | Onbekend | 0 |
| 3166 | Onbekend | 0 |
| 3167 | Onbekend | 0 |
| 3168 | Onbekend | 0 |
| 3169 | Onbekend | 0 |
| 3170 | Onbekend | 0 |
| 3171 | Onbekend | 0 |
| 3172 | Onbekend | 0 |
| 3173 | Onbekend | 0 |
| 3174 | Onbekend | 0 |
| 3175 | Onbekend | 0 |
| 3176 | Onbekend | 0 |
| 3177 | Onbekend | 0 |
| 3178 | Onbekend | 0 |
| 3179 | Onbekend | 0 |
| 3180 | Onbekend | 0 |
| 3181 | Onbekend | 0 |
| 3182 | Onbekend | 0 |
| 3183 | Onbekend | 0 |
| 3184 | Onbekend | 0 |
| 3185 | Onbekend | 0 |
| 3186 | Onbekend | 0 |
| 3187 | Onbekend | 0 |
| 3188 | Onbekend | 0 |
| 3189 | Onbekend | 0 |
| 3190 | Onbekend | 0 |
| 3191 | Onbekend | 0 |
| 3192 | Onbekend | 0 |
| 3193 | Onbekend | 0 |
| 3194 | Onbekend | 0 |
| 3195 | Onbekend | 0 |
| 3196 | Onbekend | 0 |
| 3197 | Onbekend | 0 |
| 3198 | Onbekend | 0 |
| 3199 | Onbekend | 0 |
| 3200 | Onbekend | 0 |
| 3201 | Onbekend | 0 |
| 3202 | Onbekend | 0 |
| 3203 | Onbekend | 0 |
| 3204 | Onbekend | 0 |
| 3205 | Onbekend | 0 |
| 3206 | Onbekend | 0 |
| 3207 | Onbekend | 0 |
| 3208 | Onbekend | 0 |
| 3209 | Onbekend | 0 |
| 3210 | Onbekend | 0 |
| 3211 | Onbekend | 0 |
| 3212 | Onbekend | 0 |
| 3213 | Onbekend | 0 |
| 3214 | Onbekend | 0 |
| 3215 | Onbekend | 0 |
| 3216 | Onbekend | 0 |
| 3217 | Onbekend | 0 |
| 3218 | Onbekend | 0 |
| 3219 | Onbekend | 0 |
| 3220 | Onbekend | 0 |
| 3221 | Onbekend | 0 |
| 3222 | Onbekend | 0 |
| 3223 | Onbekend | 0 |
| 3224 | Onbekend | 0 |
| 3225 | Onbekend | 0 |
| 3226 | Onbekend | 0 |
| 3227 | Onbekend | 0 |
| 3228 | Onbekend | 0 |
| 3229 | Onbekend | 0 |
| 3230 | EEV2 (injection) control mode (0=ext, 1=auto) | 1 |
| 3231 | EEV opening during defrost | 135 |
| 3232 | EEV1 initial opening after homing | 135 |
| 3233 | Onbekend | 0 |
| 3234 | EEV opening during 4-way valve switching | 0 |
| 3235 | Baud Rate UART3 | 4 |
| 3236 | Parity Check UART3 | 1 |
| 3237 | Working mode of bottom plate heater | 2 |
| 3238 | Ambient temperature to start bottom plate heater | 34 |
| 3239 | Stop hysteresis of bottom plate heater | 3 |
| 3240 | Ambient temperature to start crankcase heater | 33 |
| 3241 | Crankcase heater restart temp / V1 stop hysteresis | 33 |
| 3242 | Onbekend | 0 |
| 3243 | Onbekend | 0 |
| 3244 | Onbekend | 0 |
| 3245 | High pressure sensor type (0=none, 1=50bar, 2=46bar) | 1 |
| 3246 | Low pressure sensor enable | 1 |
| 3247 | High pressure protection shutdown value (bar) | 31 |
| 3248 | Low pressure protection shutdown value (0.1 bar) | 4 |
| 3249 | Fan control mode (0=external, 1=auto) | 1 |
| 3250 | Fan control method (0=speed table, !=0=relays) | 0 |
| 3251 | Fan speed heating step 1 / defrost high pressure | 40 |
| 3252 | Fan speed heating step 2 | 44 |
| 3253 | Fan speed heating step 3 | 48 |
| 3254 | AC current shutdown threshold cooling | 16 |
| 3255 | AC current speed-down threshold cooling | 15 |
| 3256 | AC current release threshold cooling | 14 |
| 3257 | AC current shutdown threshold heating | 16 |
| 3258 | AC current speed-down threshold heating | 15 |
| 3259 | AC current release threshold heating | 14 |
| 3260 | Discharge temp shutdown threshold | 140 |
| 3261 | Discharge temp fast speed-down threshold | 135 |
| 3262 | Discharge temp speed-down / EEV open threshold | 130 |
| 3263 | Discharge temp protection release threshold | 125 |
| 3264 | Outdoor coil temp shutdown threshold cooling | 92 |
| 3265 | Outdoor coil temp speed-down threshold cooling | 89 |
| 3266 | Outdoor coil temp hold threshold cooling | 87 |
| 3267 | Outdoor coil temp release threshold cooling | 82 |
| 3268 | High pressure speed-down threshold (bar) | 30 |
| 3269 | High pressure frequency hold threshold (bar) | 28 |
| 3270 | High pressure protection release threshold (bar) | 26 |
| 3271 | Defrost algorithm 4: defrost interval (min) | 45 |
| 3272 | Onbekend | 12 |
| 3273 | Cooling frost protection: strong speed-down temp | 32 |
| 3274 | Cooling frost protection: 45Hz limit temp | 33 |
| 3275 | Defrost control mode (0=master, 1=auto ODU) | 1 |
| 3276 | Defrost algorithm mode | 4 |
| 3277 | Enter defrost outdoor coil temp 1 (ambient >= 3C) | 27 |
| 3278 | Exit defrost outdoor coil temperature | 47 |
| 3279 | Maximum defrosting time (min) | 8 |
| 3280 | Defrost 4-way valve switching frequency (Hz) | 36 |
| 3281 | Defrost running frequency (Hz) | 61 |
| 3282 | Frequency limitation control for ambient outdoor temp | 1 |
| 3283 | Max compressor step cooling ambient < 0C | 0 |
| 3284 | Max compressor step cooling ambient 0-12C | 2 |
| 3285 | Max compressor step cooling ambient 12-18C | 3 |
| 3286 | Max compressor step cooling ambient 18-24C | 6 |
| 3287 | Max compressor step cooling ambient 24-30C | 10 |
| 3288 | Max compressor step cooling ambient 30-41C | 10 |
| 3289 | Max compressor step cooling ambient 41-45C | 7 |
| 3290 | Max compressor step cooling ambient 45-51C | 4 |
| 3291 | Max compressor step cooling ambient 51-65C | 1 |
| 3292 | Max compressor step cooling ambient >= 65C | 0 |
| 3293 | Max compressor step heating below min ambient | 0 |
| 3294 | Max compressor step heating min ambient to 12C | 10 |
| 3295 | Max compressor step heating ambient 12-20C | 8 |
| 3296 | Max compressor step heating ambient 20-24C | 5 |
| 3297 | Max compressor step heating ambient 24-28C | 3 |
| 3298 | Max compressor step heating ambient 28-46C | 2 |
| 3299 | Max compressor step heating ambient >= 46C | 0 |
| 3300 | Onbekend | 0 |
| 3301 | Inverter config byte 2 (low byte of 2114) | 0 |
| 3302 | Fan speed heating step 4 | 52 |
| 3303 | Fan speed heating step 5 | 53 |
| 3304 | Fan speed heating step 6 | 56 |
| 3305 | Fan speed heating step 7 | 68 |
| 3306 | Fan speed heating step 8 | 72 |
| 3307 | Fan speed heating step 9 (Max fan setpoint) | 78 |
| 3308 | Defrost algo 4 min runtime (min) / Doc: Low noise switch | 5 |
| 3309 | Low noise mode max fan speed | 62 |
| 3310 | Fan configuration (0=dual fan, !=0=single fan) | 1 |
| 3311 | EEPROM parameter set version | 114 |
| 3312 | Defrost algorithm 3: cold mode ambient threshold | 10 |
| 3313 | Defrost algorithm 4: max runtime before defrost (min) | 180 |
| 3314 | Defrost algorithm 4: ambient threshold for exit criteria | 5 |
| 3315 | Defrost algorithm 4: min interval for criterion (min) | 25 |
| 3316 | Defrost algorithm 3: change threshold | 40 |
| 3317 | Setting of the model (main PCB) address (unused in 1.30) | 2 |
| 3318 | Onbekend | 0 |
| 3319 | Defrost fan turn-on high pressure threshold (bar) | 29 |
| 3320 | Oil return running frequency (Hz) | 61 |
| 3321 | Fan speed cooling step 1 (Fan low setpoint 1) | 62 |
| 3322 | Fan speed cooling step 2 (Fan low setpoint 2) | 62 |
| 3323 | Fan speed cooling step 3 (Fan low setpoint 3) | 62 |
| 3324 | Fan speed cooling step 4 (Fan mid setpoint 1) | 68 |
| 3325 | Fan speed cooling step 5 (Fan mid setpoint 2) | 68 |
| 3326 | Fan speed cooling step 6 (Fan mid setpoint 3) | 68 |
| 3327 | Fan speed cooling step 7 (Fan setpoint high 1) | 72 |
| 3328 | Fan speed cooling step 8 (Fan setpoint high 2) | 72 |
| 3329 | Fan speed cooling step 9 (Fan setpoint high 3) | 72 |
| 3330 | Grid undervoltage shutdown threshold (V) | 140 |
| 3331 | Grid voltage band 3 threshold (V) | 156 |
| 3332 | Grid voltage band 2 threshold (V) | 170 |
| 3333 | Grid voltage band 1 threshold (V) | 188 |
| 3334 | Max compressor step in voltage band 3 | 2 |
| 3335 | Max compressor step in voltage band 2 | 5 |
| 3336 | Max compressor step in voltage band 1 | 6 |
| 3337 | Enter defrost outdoor coil temp 2 (ambient -3 to 3C) | 27 |
| 3338 | Enter defrost outdoor coil temp 3 (ambient -10 to -3C) | 25 |
| 3339 | Enter defrost outdoor coil temp 4 (ambient < -10C) | 18 |
| 3340 | Defrost exit confirmation time (s) | 10 |
| 3341 | Immediate defrost exit outdoor coil temp | 55 |
| 3342 | Fixed 45 min defrost interval at ambient -3 to 3C enable | 1 |
| 3343 | Compressor current speed-down threshold | 25 |
| 3344 | Compressor current release threshold | 22 |
| 3345 | Inverter word 11 speed-down threshold | 147 |
| 3346 | Inverter word 11 release threshold | 140 |
| 3347 | Oil return timer frequency threshold / ramp frequency (Hz) | 45 |
| 3348 | Oil return interval cooling & heating outside 0-14C (min) | 120 |
| 3349 | EEV opening during oil return | 150 |
| 3350 | Onbekend | 0 |
| 3351 | Onbekend | 0 |
| 3352 | Onbekend | 0 |
| 3353 | Onbekend | 0 |
| 3354 | Onbekend | 0 |
| 3355 | Onbekend | 0 |
| 3356 | Model/capacity identity code (shown in 11006) | 0 |
| 3357 | Baud Rate UART1 | 2 |
| 3358 | Parity Check UART1 | 0 |
| 3359 | EEV standby position band 1 (ambient >= 30C) | 50 |
| 3360 | EEV standby position band 2 (ambient 10 to 30C) | 100 |
| 3361 | EEV standby position band 3 (ambient -5 to 10C) | 135 |
| 3362 | EEV standby position band 4 (ambient -15 to -5C) | 175 |
| 3363 | EEV standby position band 5 (ambient < -15C) | 200 |
| 3364 | EEV start heating: water < 30C, ambient >= 30C | 105 |
| 3365 | EEV start heating: water < 30C, ambient 10-30C | 145 |
| 3366 | EEV start heating: water < 30C, ambient 5-10C | 155 |
| 3367 | EEV start heating: water < 30C, ambient -5 to 5C | 170 |
| 3368 | EEV start heating: water < 30C, ambient -10 to -5C | 170 |
| 3369 | EEV start heating: water < 30C, ambient -20 to -15C | 170 |
| 3370 | EEV start heating: water 30-45C, ambient >= 30C | 100 |
| 3371 | EEV start heating: water 30-45C, ambient 10-30C | 125 |
| 3372 | EEV start heating: water 30-45C, ambient 5-10C | 155 |
| 3373 | EEV start heating: water 30-45C, ambient -5 to 5C | 160 |
| 3374 | EEV start heating: water 30-45C, ambient -10 to -5C | 185 |
| 3375 | EEV start heating: water 30-45C, ambient -20 to -15C | 190 |
| 3376 | EEV start heating: water >= 45C, ambient >= 30C | 125 |
| 3377 | EEV start heating: water >= 45C, ambient 10-30C | 150 |
| 3378 | EEV start heating: water >= 45C, ambient 5-10C | 160 |
| 3379 | EEV start heating: water >= 45C, ambient -5 to 5C | 165 |
| 3380 | EEV start heating: water >= 45C, ambient -10 to -5C | 190 |
| 3381 | EEV start heating: water >= 45C, ambient -20 to -15C | 195 |
| 3382 | EEV start cooling: water >= 18C, ambient >= 30C | 10 |
| 3383 | EEV start cooling: water >= 18C, ambient 20-30C | 10 |
| 3384 | EEV start cooling: water >= 18C, ambient < 20C | 10 |
| 3385 | EEV start cooling: water 12-18C, ambient >= 30C | 10 |
| 3386 | EEV start cooling: water 12-18C, ambient 20-30C | 10 |
| 3387 | EEV start cooling: water 12-18C, ambient < 20C | 10 |
| 3388 | EEV start cooling: water < 12C, ambient >= 30C | 10 |
| 3389 | EEV start cooling: water < 12C, ambient 20-30C | 10 |
| 3390 | EEV start cooling: water < 12C, ambient < 20C | 10 |
| 3391 | Discharge superheat upper limit for 0K suction target | 38 |
| 3392 | Max suction superheat target in discharge cascade | 11 |
| 3393 | Suction superheat interpolation base in cascade | 27 |
| 3394 | Base target suction superheat (K) | 10 |
| 3395 | Extra target superheat after start (360s decay) | 10 |
| 3396 | Extra target superheat after defrost (480s decay) | 10 |
| 3397 | Fallback suction temp offset on sensor fault | 5 |
| 3398 | Low water temp threshold for EEV start correction | 45 |
| 3399 | Onbekend | 0 |
| 3400 | Onbekend | 0 |
| 3401 | Onbekend | 0 |
| 3402 | Onbekend | 0 |
| 3403 | Onbekend | 0 |
| 3404 | Onbekend | 0 |
| 3405 | Onbekend | 0 |
| 3406 | Onbekend | 0 |
| 3407 | Onbekend | 0 |
| 3408 | Onbekend | 0 |
| 3409 | Onbekend | 0 |
| 3410 | Onbekend | 0 |
| 3411 | Onbekend | 0 |
| 3412 | Onbekend | 0 |
| 3413 | Onbekend | 0 |
| 3414 | Emergency pump duty cycle on comm loss (%) | 0 |
| 3415 | Defrost algo 4: evap temp diff ambient 0 to 9C | 17 |
| 3416 | Defrost algo 4: evap temp diff ambient -5 to 0C | 18 |
| 3417 | Defrost algo 4: evap temp diff ambient -10 to -5C | 18 |
| 3418 | Defrost algo 4: evap temp diff ambient -15 to -10C | 19 |
| 3419 | Defrost algo 4: evap temp diff ambient -20 to -15C | 20 |
| 3420 | Defrost algo 4: evap temp diff ambient -23 to -20C | 22 |
| 3421 | Defrost algo 4: evap temp diff ambient < -23C | 24 |
| 3422 | Defrost algo 4: evap temp diff ambient < 7C after timer | 14 |
| 3423 | Defrost algo 4: exit coil temp at low ambient | 55 |
| 3424 | Defrost fan drip time (s) | 0 |
| 3425 | Onbekend | 0 |
| 3426 | Onbekend | 0 |
| 3427 | Defrost algo 4: exit confirmation time 1 (s) | 3 |
| 3428 | Defrost algo 4: exit confirmation time 2 (s) | 3 |
| 3429 | EEV feedforward coeff A high byte | 0 |
| 3430 | EEV feedforward coeff A low byte | 190 |
| 3431 | EEV feedforward term B high byte | 3 |
| 3432 | EEV feedforward term B low byte | 198 |
| 3433 | EEV feedforward duration after freq change (s) | 30 |
| 3434 | Temporary frequency ceiling after mode change/defrost (Hz) | 45 |
| 3435 | Temporary frequency ceiling duration (s) | 30 |
| 3436 | Onbekend | 0 |
| 3437 | Oil return duration at target frequency (min) | 2 |
| 3438 | Oil return maximum duration (min) | 3 |
| 3439 | Oil return pre-ramp duration at 45Hz (s) | 30 |
| 3440 | Oil return post-ramp duration at 45Hz (s) | 30 |
| 3441 | Onbekend | 0 |
| 3442 | Condensation temp limit heating 3 (V2) | 0 |
| 3443 | Condensation temp limit heating 4 (V2) | 0 |
| 3444 | Onbekend | 0 |
| 3445 | Onbekend | 0 |
| 3446 | Onbekend | 0 |
| 3447 | Onbekend | 0 |
| 3448 | Onbekend | 0 |
| 3449 | Onbekend | 0 |
| 3450 | EEV feedforward coeff C high byte | 0 |
| 3451 | EEV feedforward coeff C low byte | 169 |
| 3452 | Onbekend | 0 |
| 3453 | Onbekend | 0 |
| 3454 | Onbekend | 0 |
| 3455 | Onbekend | 0 |
| 3456 | Min. flow rate (unused by firmware) | 0 |
| 3457 | Extra input / R290 leak sensor enable | 0 |
| 3458 | L1, L2, L3 & 4-way valve relay control by master (2010) | 0 |
| 3459 | Water flow sensor type (0=none, 1=Sika, 2=Huba, 3=10L/min/V) | 0 |
| 3460 | Second expansion valve (EEV2 injection) enable | 0 |
| 3461 | EEV2 control interval | 15 |
| 3462 | EEV2 maximum opening | 44 |
| 3463 | EEV2 minimum opening | 30 |
| 3464 | EEV2 active ambient temperature threshold | 12 |
| 3465 | EEV2 minimum compressor frequency (Hz) | 45 |
| 3466 | EEV2 start opening (x10) | 42 |
| 3467 | EEV2 active control discharge temp threshold | 97 |
| 3468 | EEV2 turn-on discharge temp threshold | 45 |
| 3469 | Onbekend | 80 |
| 3470 | EEV2 gain on discharge temp error | 2 |
| 3471 | EEV2 gain on discharge temp change | 1 |
| 3472 | EEV2 target setting ambient < -20C | 31 |
| 3473 | EEV2 target setting ambient -20 to 0C | 31 |
| 3474 | EEV2 target setting ambient 0 to 20C | 31 |
| 3475 | EEV2 target setting ambient 20 to 40C | 31 |
| 3476 | EEV2 target setting ambient >= 40C | 31 |
| 3477 | Target discharge superheat base (K) | 15 |
| 3478 | Target discharge superheat slope per step (0.1 K) | 5 |
| 3479 | EEV PID control interval (s) | 15 |
| 3480 | EEV maximum opening in auto mode (x2 steps) | 215 |
| 3481 | EEV minimum opening in auto mode (x2 steps) | 10 |
| 3482 | EEV max step size per interval | 15 |
| 3483 | EEV PID proportional gain (P) | 6 |
| 3484 | EEV PID integral gain (I) | 5 |
| 3485 | EEV PID derivative gain (D) | 4 |
| 3486 | Onbekend | 0 |
| 3487 | Onbekend | 0 |
| 3488 | Onbekend | 0 |
| 3489 | Onbekend | 0 |
| 3490 | Onbekend | 0 |
| 3491 | Onbekend | 0 |
| 3492 | Inverter communication protocol type | 2 |
| 3493 | Inverter protocol variant (0=voltage limit active) | 0 |
| 3494 | Water temperature sensors on ODU enable | 0 |
| 3495 | Water flow correction value (unused by firmware) | 0 |
| 3496 | Inverter config byte 1 (high byte of 2114) | 0 |
| 3497 | DC water pump control mode | 0 |
| 3498 | Refrigerant type (0=R32/R410A, 1=R290) | 1 |
| 3499 | Heating min ambient temperature base (offset 30) | 5 |
| 3500 | Heating min ambient temperature reduction | 0 |
| 3501 | Heating min ambient temperature extra hysteresis | 4 |
| 3502 | Water pump high speed power (unused by firmware) | 0 |
| 3503 | Water pump medium speed power (unused by firmware) | 0 |
| 3504 | Water pump low speed power (unused by firmware) | 0 |
| 3505 | DC fan high speed power (unused by firmware) | 0 |
| 3506 | DC fan medium speed power (unused by firmware) | 0 |
| 3507 | DC fan low speed power (unused by firmware) | 0 |
| 3508 | Heating outlet temp diff correction (unused by firmware) | 0 |
| 3509 | Cooling outlet temp diff correction (unused by firmware) | 0 |
| 3510 | Checksum low byte (CRC-16/Modbus) | 146 |
| 3511 | Checksum high byte (CRC-16/Modbus) | 201 |
512 registers getoond